K545
Login to see priceSyncro I/O – 4 Way Conventional Detection Zone Module
Expansion board which can be used to replace a conventional detection panel interfacing circuits directly to a Syncro addressable system
4 x monitored conventional detection zones, max 30 devices per zone
2 x Monitored sounder outputs – Max 1 Amp per circuit
1 x VFCO Fire relay – rated 1A @ 30V DC
1 x VFCO Fault relay – rated 1A @ 30V DC
2 wire RS485 Communication with panel
Panel will support max 32 expansion Boards
Kentec Syncro 4 Way Conventional Detection Zone Module K545
To further enhance the versatility of the Syncro fire alarm system, four conventional detection circuits can be connected with up to 30 detectors per circuit. Conventional control panels can be replaced with this simple module and existing conventional systems can be interfaced directly to modern analogue addressable control systems and networks. A fail safe mode ensures that the detection inputs will still operate the sounder outputs and fire contact if communication to the Syncro panel is lost. Consideration must be taken as to the loading on the main panel.
Features:
- 4 monitored detection zone inputs
- 2 monitored sounder outputs
- Volt free fire contact
- Volt free fault contact
- Local power supply fault input
- RS485 comms connection to Syncro Fire Alarm Panel
- Individual fault and operated indications for inputs and outputs
- Directly replaces a conventional control panel when integrating into an analogue addressable system
- Can be used with other Syncro I/O modules on the same panel
- Compatible with Syncro AS panels